OK, the pressure switch has nothing to do with the blanket over the return air, just a coincidence.

On power up with a call for heat, the exhaust motor should start first.

Check the pressure switch tubing for obstructions

Verify that the condensate lines are clear

Check the exhaust pipe for obstructions

If those check out ok then you will need to test the pressure(negative pressure) at the switch to move further.

If you are not sure what I am talking about let me know and I will try to explain it another way.

 