What kind of schmo working on Sub-Zero's doesn't carry a condenser fan motor with him? Is this guy authorized? I buy them by the dozen. I find they fail right around the two-year mark or later.

The divider between the compartments as well as the trim around the frame will get warm when the condenser fan motor fails, sometimes it can be too hot to touch. I am surprised it was able to hold temperature with a non-running condenser fan for such a long time.

I also find a lot of times the high head pressure caused by the lack of proper condenser operation will cause a borderline ref evaporator to leak. I do many combos like this.