View single post by SELFINC
 Posted: Thu Jun 29th, 2006 08:33 am
PM Quote Reply Full Topic
SELFINC



Joined: Wed May 31st, 2006
Location: HOLLISTER, California USA
Posts: 14
Status: 
Offline
:D Howdy! The problem with 90% of these I find & by the way, I am an authorized Sub Zero Servicer...... The evaporator is the problem. Made of copper & the replacement from a new vendor is not copper. Sub Zero is well aware of the problem. You most likely have an ice ball on the top left corner of the evap that grows out in to the refer compartment & then falls off. I learned the hard way that changing the drier & recharging only lasts 6 months to a year & then it re-occurs. You will need to replace the evaporator & make sure your part supplier is selling you new stock & not old, you dont want to put in another copper evap.