dkpd1581
|
Your fan - in the heat mode - is controlled by the combination fan/limit switch made by Honeywell. See picture number 4 from above with the caption underneath "Thermo-Switch and Gas Valve." If the fan runs in ON and in AC, then check out your combination fan/limit switch and see that the round dial on it actually rotates in a clockwise position while the burners are lit. When it reaches a certain temperature the dial will turn past an adjustable pin in the face. If it passes that location and the fan does not come on, I would suggest replacing the device. If you could scan in and attach the wire diagram as a PDF in this thread, that might help a bunch of people. Last edited on Thu Dec 18th, 2008 10:39 pm by dkpd1581 ____________________ |
||||||||||||
|
| |||||||||||||